LINED CLEVIS HANGERS

Construction Features
  • Designed for Chilled Water Pipework and
    Fire Fighting Systems.
  • Design permits vertical adjustment of pipe
    after installation.
  • Hanger load nut above Clevis must be
    tightened securely to ensure proper
    hanger performance.
  • EPDM Lining for suppression of sound and vibrations.

Technical Data

Material : Carbon Steel
Electrogalvanized as per ASTM B 633 Standards

Part No. Pipe Size Max Load Dimensions (mm)
Inches Kgs Upper Steel Lower Steel Rod Hole
Size
Bolt Size H D
DMC122022 1/2" 275 3x25 3x25 10 M8x60 73 22
DMC122028 3/4" 275 3x25 3x25 10 M8x68 79 28
DMC122035 1" 275 3x25 3x25 10 M8x78 85 35
DMC122040 1-1/4" 275 3x25 3x25 10 M8x82 95 42
DMC122048 1-1/2" 275 3x25 3x25 10 M8x88 103 48
DMC122060 2" 275 3x25 3x25 10 M10x110 120 60
DMC122075 2-1/2" 525 4x25 4x25 10 M10x125 149 73
DMC122090 3" 525 4x25 4x25 10 M10X140 158 89
DMC122105 3-1/2" 525 4x25 4x25 10 M10x155 176 105
DMC122115 4" 650 6x32 6x32 10 M10X170 201 115
DMC122140 5" 650 6x32 6x32 12 M12X195 235 140
DMC122168 6" 875 6x32 6x32 12 M12x225 269 168
DMC122219 8" 900 6x40 5x40 12 M12x275 341 219
DMC122273 10" 1600 6x40 6x40 16 M16x360 422 273
DMC122323 12" 1700 9x50 6x50 20 M20x420 493 323
DMC122355 14" 1900 9x50 6x50 20 M20x455 559 355
DMC122406 16" 2000 12x65 6x65 24 M24X510 613 406
DMC122457 18" 2150 12x65 6x65 24 M24x555 678 457
DMC122508 20" 2200 12x75 9x75 30 M24X610 718 508
DMC122610 24" 2200 16x75 9x75 30 M24X710 853 610
DMC122755 30" 2700 19x75 9x75 30 M24x890 998 755

Measurements are subject to 5% tolerance
The Sizes of the Clevis hangers can be modified to be used with Rubber Support Inserts.
Custom made Clevis hanger are also available.


Manufacturers of quality pipe support systems